Operating procedures
20
Setting the Tn (resetting time)
1. Press the key .
The indicator light blinks and the effective value for Tn
appears on the MULTI-DISPLAY (LED).
2. Follow the instructions
3. for
4. (example: 1200 s).
Setting range for Tn: 1 to 9998 s.
With Tn set to 9999, the integral part of the controller is
deactivated (use of a P or PD type controller).
Setting the Tv (lead time)
1. Press the key .
The indicator light blinks and the effective value for Tv
appears on the MULTI-DISPLAY (LED).
2. Follow the instructions
3. for
4. (example: 120 s).
Setting range for Tv: 0 to 1000 s.
With Tv set to 0 eingestellt, the differential part of the
controller is deactivated (use of a P or PI type controller).